A wide range of fieldbus modules are available (contact your local Baldor office or distributor for a
full list):
Carrier card: OPT-MF-030
DeviceNet: OPT-FB-001 (Anybus AB6201)
PROFIBUS DP-V1: OPT-FB-002 (Anybus AB6200)
EtherNet/IP: OPT-FB-004 (Anybus AB6214)
Modbus/TCP: OPT-FB-005 (Anybus AB6213)
PROFINET IO: OPT-FB-006 (Anybus AB6215)
Separate application notes are available on setting up these alternative Fieldbus Options.
Modbus/TCP Function Codes
The Modbus/TCP Fieldbus Option supports the following Modbus function codes:
1 - Read Coils
2 - Read Discrete Inputs
3 - Read holding Registers
4 - Read Input Registers
5 - Write Single Coil
6 - Write Single Register
15 - Write Multiple Coils
16 - Write Multiple Registers
23 - Read/Write Multiple Registers
43 - Read Device Identification
Modbus/TCP Register Implementations
The Modbus/TCP Holding (4x) Registers are mapped as follows:
Modbus Register Range Contents
0000 – 00FF hex (0 to 255 dec) Read Process Data (data written by PLC)
0100 – 01FF hex (256 to 511 dec) Write Process Data (data read by PLC)
0210 – FFFF hex (528 to 65535 dec) Application Data Instances (ADIs)
The Modbus/TCP Input (3x) Registers are mapped as follows:
Modbus Register Range Contents
0000 – 00FF hex (0 to 255 dec) Write Process Data (e.g. Input register 0 is
mapped to Modbus Register 0100 hex)
The Modbus/TCP Discrete Input (1x) Registers are mapped as follows:
Modbus Register Range Contents
0000 – 0FFF hex (0 to 4095 dec) Write Process Data (e.g. Discrete Input
register 0 is mapped to Modbus Register 0100
hex)
The Modbus/TCP Discrete Output (0x) Registers are mapped as follows:
Modbus Register Range Contents
0000 – 0FFF hex (0 to 4095 dec) Read Process Data (e.g. Discrete Output
register 0 is mapped to Modbus Register 0000
hex)